Eliminate of Frequent Malfunction

FAQ: The fan of humidifier doesn't work

Maintenance Method:

1. The axial flow fan is faulty and the axial flow fan shall be replaced.

2. Delay relay failure, replace relay.


FAQ: Ultrasonic humidifier shows E1 or -25.0

Maintenance Method:

1. Check if the humidity sensor is plugged in or not connected.

2. Check if the air interface is in poor contact and tighten the cable.

3. The humidity sensor is faulty and the humidity sensor shall be replaced.



FAQ: The ultrasonic humidifier indicator is on but the meter is not showing


Maintenance Method:

1. Check if the connecting cable behind the instrument panel is loose.

2. The instrument controller is faulty and the meter shall be replaced.


FAQ: Ultrasonic humidifiers sometimes trip when turned on

Maintenance Method:

1. The power plug is not grounded

2. The air switch power is too small, 3kg-9kg with 15A or 12kg-21kg with 32A or 24kg-30kg with 55A or so, the above models are more than 60A, depending on the working conditions.



FAQ: Water leakage at the overflow of the ultrasonic humidifier (overflow)


Maintenance Method:

1. Clean the water level switch of the water tank.

2. There is foreign matter in the water inlet solenoid valve, remove the solenoid valve spool or replace the water inlet solenoid valve.

3. The water inlet float valve is broken or re-adjusted


FAQ: Ultrasonic humidifier does not generate fog

Maintenance Method:

1. The atomizer and the water tank are not cleaned for a long time, so the water quality is too dirty to cause atomization. The water tank and atomizer should be cleaned.

2. the water quality is too bad and turbid (hard water), you need to install filter soft water purification.

3. The humidity setting is incorrect, and the humidity is set to be 2% higher than the current ambient humidity.

4. The water level of the water tank is abnormally high or low. Check the solenoid valve, the water level float switch or drain the water and then re-inject the water automatically.

5. the axial fan does not turn, replace the axial fan

6. The rectifier board has no 48 volt DC voltage output and replaces the rectifier board or fuse.

7. The atomizer or atomizer is aged, and the atomizer or atomizer is replaced.

8. Check if the toroidal transformer has a 36 volt AC output.

9. Check if the meter controller has an AC 220 V output voltage at the output.



Contact Us:

Dear Customers:

We are professional manufacturer for humidifiers, mist makers and dehumidifiers.

Contact us to get the direct factory price.

May will reply you efficiently upon your inquiry.

Mobil: 0086-15257589302

Email: sales@conloon.com

Skype: conloon


Hot Tags: mushroom humidifierChina, manufacturers, suppliers, factory, wholesale

Send Inquiry

(0/10)

clearall